RCT 1000VA ON-LINE SINE WAVE 2U RACKMOUNT UPS


  • Capacity: 1000VA / 800W
  • Frequency Range: 40 Hz ~ 70 Hz
  • Battery Type: 12 V / 9 Ah
  • Pure Sinewave

RCT 1000VA On-Line Sine Wave 2U Rackmount UPS (RCT-1000-WPRU) has a wide input voltage range and an available converter mode.

Features

This UPS can charge up to 90% in battery capacity within a 4 hour period. This UPS has a built-in Microprocessor control that guarantees high reliability. It also includes free monitoring software as well as Overload, discharge and overcharge protection.

Note

A UPS is not designed to provide continuous power, it allows a computer or device to keep running for a short period of time when the primary power source is lost.

SKU: RCT-1000-WPRU Categories: ,

Capacity
1000 VA / 800 W

Input
Voltage
100/110/115/120/127 VAC or 200/208/220/230/240 VAC

Voltage Range
55-150 VAC or 110-300 VAC @ 50% load, 85-140 VAC or 160-280 VAC @ 100% load

Frequency Range
40 Hz ~ 70 Hz

Power Factor
≥ 0.99 @ nominal voltage (100% load)

Output
Output Voltage
100/110/115/120/127 VAC or 200/208/220/230/240 VAC

AC Voltage Regulation (Batt. Mode)
±1%

Frequency Range (Synchronized Range)
47~53 Hz or 57~63 Hz

Frequency Range (Batt. Mode)
50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz

Current Crest Ratio
3:1 (max.)

Harmonic Distortion
≤ 3 % THD (Linear Load) ; ≤ 6 % THD (Non-linear Load)

Transfer Time
AC Mode to Batt. Mode
Zero

Inverter to Bypass
4 ms (Typical)

Waveform (Batt. Mode)
Pure Sinewave

Efficiency
AC Mode
88 %

Battery Mode
83%

Battery
Standard Model
Battery Type
12 V / 9 Ah

Numbers
2

Typical Recharge Time
4 hours recover to 90% capacity

Charging Current (max.)
1 A

Charging Voltage
27.4 VDC ± 1%

Long-run Model
Battery Type
Depending on the applications running

Numbers
2    3

Charging Current (max.)
1A/2A/4A/6A (Adjustable)

Charging Voltage
27.4 VDC ± 1%    41.0 VDC ± 1%

Indicators
LCD Display
UPS Status, Load Level, Battery Level, Input/Output Voltage, Discharge timer and Fault conditions

Alarm
Battery Mode
Sounding every 4 seconds

Low Battery
Sounding every second

Overload
Sounding every twice second

Fault
Continuously Sounding

Physical
Standard Model
Dimensions, D X W X H(mm)
310  x 438 x 88[2U]

Net Weight (kgs)
12

Long-run Model
Dimensions, D X W X H(mm)
310  x 438 x 88[2U]

Net Weight (kgs)
9

Environment
Humidity
20-90 % RH @ 0- 40° (non-condensing)

Noise Level
Less than 50dB @ 1 meter

Management
Smart RS-232 and USB
Supports Windows® 2000/2003/XP/Vista/2008. Windows® 7/8, Linus and MAC

Optional SNMP
Power management from SNMP manager and web browser

Based on 0 reviews

0.0 overall
0
0
0
0
0

Be the first to review “RCT 1000VA ON-LINE SINE WAVE 2U RACKMOUNT UPS”